Helmholz PN/CAN Layer 2 Protocol Gateway

Easy and straightforward connection of CAN devices to PROFINET
Produktnummer: 700-671-PNC01
BESKRIVNING

On the PROFINET network, the PN/CAN gateway is a PROFINET I/O device and supports transfer rates up to 100 Mbps full duplex; and up to 1 Mbps on the CAN bus.
The I/O data of the CAN participants is transparently displayed in a freely configurable manner on the PROFINET network and can thus be processed directly in the PLC. The PN/CAN gateway is integrated with a GSDML file in the hardware configurator and can be fully configured there. No other software tools for configuration or handling blocks for programming are necessary, making gateway use straightforward.
The features of the PN/CAN gateway are rounded out by MRP (media redundancy), as well as extensive diagnostic functions and an interface for online diagnostics.

With the Layer 2 PN/CAN gateway, CAN devices can be connected using proprietary CAN protocols, including devices with the SAE J1939 protocol, among others.

  • SDO communication, emergency messages, participant monitoring with heartbeat and node guarding
  • Easy configuration using a GSDML file; no handling blocks or configuration software necessary
  • Supports CAN Layer 2 protocol
  • Up to 512 CAN messages can be configured
  • SAE J1939 protocol
SPECIFIKATIONER
General information
Order number 700-671-PNC01
Scope of delivery PN/CAN gateway, Quick Start Guide, CD with GSDML file and manual
Dimensions (DxWxH) 35 x 84 x 76 mm
Weight Approx. 160 g
PROFINET interface
Number 1
Protocol PROFINET IO as defined in IEC 61158-6-10
Physical layer Ethernet
Transmission rate 100 Mbps
I/O image size max. 1440 bytes of input / 1440 bytes of output data
Connection RJ45 socket
Features Media Redundancy Protocol (MRP), automatic addressing / topology detection (LLDP, DCP)
CAN interface
Number 1
Type ISO/DIN 11898-2 CAN High-speed physical layer
Transmission rate 50, 100, 125, 250, 500, 800, 1000 kbps
Protocol CAN Layer 2 with 11 bit or 29 bit identifier
Connection 9-pin D-sub male connector
Features Automatic and controlled reception and transmission objects, reception channel FIFO, transmission channel FIFO
USB interface
Protocol Full-speed USB 2.0 device
Connection Mini-USB
Isolation voltage 1.5 kV
Electrical isolation Yes